NGW-10K-TTH: On-Grid inverter with Energy Storage
- Self-consumption and feed-in to the grid
- Programmable supply priority for PV, Battery, or Grid
- User-adjustable battery charging current suits different types of batteries
- Programmable multiple operations modes: Grid-tie, Off-grid, and grid-tie with backup
- Built-in Timer for various modes of on/off operation
- Multiple communication for USB, RS-232, Modbus, and SNMP
- Monitoring software for real-time status display and control
- Custom-made firmware by ODM contract
- Parallel operation up to 6 units
- MODEL 10KW
- PHASE: 3-phase in / 3-phase out
- MAXIMUM PV INPUT POWER: 14850 W
- RATED OUTPUT POWER: 10000 W
- MAXIMUM CHARGING POWER: 9600 W
- GRID-TIE OPERATION
- PV INPUT (DC)
- Nominal DC Voltage / Maximum DC Voltage: 720 VDC / 900 VDC
- Start-up Voltage / Initial Feeding Voltage: 320 VDC / 350 VDC
- MPP Voltage Range: 400VDC ~ 800VDC
- Number of MPP Trackers / Maximum Input Current: 2 / 2 x 18.6A
- GRID OUTPUT (AC)
- Nominal Output Voltage: 230 VAC (P-N) / 400 VAC (P-P)
- Output Voltage Range: 184 - 265VAC* per phase
- Nominal Output Current: 14.5A per phase
- Power Factor: > 0.99
- EFFICIENCY
- Maximum Conversion Efficiency (DC/AC): 96%
- European Efficiency@ Vnominal: 95%
- PV INPUT (DC)
- OFF-GRID OPERATION
- AC INPUT
- AC Start-up Voltage/Auto Restart Voltage: 120 - 140 VAC per phase / 180 VAC per phase
- Acceptable Input Voltage Range: 170 - 280 VAC per phase
- Maximum AC Input Current: 40 A
- PV INPUT (DC)
- Maximum DC Voltage: 900 VDC
- MPP Voltage Range: 400 VDC ~ 800 VDC
- Number of MPP Trackers/Maximum Input Current: 2 / 2 x 18.6A
- BATTERY MODE OUTPUT (AC)
- Nominal Output Voltage: 230 VAC (P-N) / 400 VAC (P-P)
- Output Waveform: Pure Sinewave
- Efficiency (DC to AC): 91%
- AC INPUT
- HYBRID OPERATION
- PV INPUT (DC)
- Nominal DC Voltage / Maximum DC Voltage: 720 VDC / 900 VDC
- Start-up Voltage / Initial Feeding Voltage: 320 VDC / 350 VDC
- MPP Voltage Range: 400 VDC ~ 800 VDC
- Number of MPP Trackers/Maximum Input Current: 2 / 2 x 18.6A
- GRID OUTPUT (AC)
- Nominal Output Voltage: 230 VAC (P-N) / 400 VAC (P-P)
- Output Voltage Range: 184 - 265 VAC* per phase
- Nominal Output Current: 14.5 A per phase
- AC INPUT
- AC Start-up Voltage / Auto Restart Voltage: 120 - 140 VAC per phase / 180 VAC per phase
- Acceptable Input Voltage Range: 170 - 280 VAC per phase
- Maximum AC Input Current: 40 A
- BATTERY MODE OUTPUT (AC)
- Nominal Output Voltage: 230 VAC (P-N) / 400 VAC (P-P)
- Efficiency (DC to AC): 91%
- BATTERY & CHARGER
- Nominal DC Voltage: 48 VDC
- Maximum Charging Current: Default 60A, 10A - 200A (Adjustable)
- PV INPUT (DC)
- GENERAL
- PHYSICAL
- Dimension, D x W x H (mm): 167.2 x 500 x 622
- Net Weight (kgs): 40
- INTERFACE
- Communication Port: RS-232/USB
- Intelligent Slot: Optional SNMP, Modbus, and AS-400 cards available
- ENVIRONMENT
- Humidity: 0 ~ 90% RH (Non-Condensing)
- Operating Temperature: -10 to 55°C
- Altitude: 0 ~ 1000 m**
- PHYSICAL
NGW-10K-TTH